The input and output modules, or I/O modules, are the interface between the process station and the peripherials. They are supplied in a range of types, according to their input and output signals:
Input modules:
- R420 16 digital (on/off) inputs for 24 V AC/DC, common ground for all inputs
- R430 32 digital (on/off) inputs for 24 V AC/DC, common ground for 24 and 8 inputs
- R500 8 analogue inputs 0…10 V or 0…20 mA
- R560 8 analogue inputs Pt100, Pt1000, Ni1000, 0…5000 Ohm, 0…10 V, 0…20 mA
- R710 4 pulse counting inputs for dry contact or open collectors, up to 50 Hz, also for load shedding
Output modules:
- R220 12 low voltage relay outputs 250 V / 5 A
- R312 8 triac outputs 24 V AC binary or PWM
- R313 8 triac outputs 230 V AC binary or PWM
- R320 16 open collector binary outputs
- R330 32 open collector binary outputs
- R610 8 analogue outputs 0…10V
Combined modules:
- RCIO
- 8 analogue inputs 0..10 V or temperature sensors Pt100, Pt1000, Ni1000, 4x also 0…20 mA
- 6 analogue outputs 0..10 V
- 8 binary inputs 24 V AC/DC
- 8 low voltage relay outputs 250 V / 5 A.
- RMIO
- 4 analogue inputs Pt100, Pt1000, Ni1000, 2x also 0..10 V
- 2 analogue outputs 0..10 V
- 4 binary inputs 24 V AC/DC
- 7 binary outputs (5x relay 230 V AC, 2x SSR 24…230 V AC)
- MLIO
- 4 analogue inputs Pt100, Pt1000, Ni1000, 0..10 V, or as a DI – for dry contact
- 1 analogue output 0..10 V
- 2 relay outputs 250 V / 5 A.
- RXIO
- 16 analogue inputs 0..10 V or temperature sensors Pt100, Pt1000, Ni1000, 8x also 0…20 mA
- 8 analogue outputs 0..10 V
- 32 binary inputs 24 V AC
- 32 relay outputs 250 V / 5 A.
- MW240-B
- Small I/O module for flush-box installation, with internal logic for control of 2 light groups or a blinds motor.
- 2 DI for dry contacts
- 2 DO – relay 230 V / 4 A
- MW241
- Same as MW240-B, but solid state relays instead of mechanical relays. The module is used for switching of LED light power supplies, which show capacitive characteristics and mechanical relays should not be used here.
Compatibility for replacement of older M… modules by new R… modules, IRC controllers and converters is as follows:
Old product |
New product |
Compatibility |
M005 | R005 | New housing, new operating temperature range |
M012 | R012 | New housing, new operating temperature range |
M020 | R020 | New housing, new operating temperature range |
M025 | R025 | New housing, new operating temperature range |
M031 | R031 | New housing, new operating temperature range |
M035 | R035 | New housing, new operating temperature range |
M040 | R040 | New housing, new operating temperature range |
- | R060 | Modbus TCP – MP-Bus converter (Belimo actuators) |
- | R065 | Modbus TCP – DMX (control of lights over DMX512) |
M085 | R085 | New housing, new operating temperature range |
M086 | R086 | New housing, new operating temperature range |
M090 | R091 | New also as multimaster. SW backward compatible. New housing: 4 DIN modules instead of 2 DIN modules! |
M095 | R095 | New housing, new operating temperature range. New housing: 4 DIN modules instead of 2 DIN modules. Only 300 and 2400 bps. |
M096 | R096 | New housing, new operating temperature range. New housing: 4 DIN modules instead of 2 DIN modules. Only 300 and 2400 bps. |
MMIO | RMIO | Terminal reconnection necessary if module replaced. DI/AI/AO/DO6,7 now for 1,5 mm² wires, SSR now also for DC load, addressing also over DIP switches |
MXIO | RXIO | Redesign of housing only |
MCIO2 | RCIO | Redesign of housing only |
ECIO2 | ICIO205 | Not a 100 % replacement: customized application for ICIO205 necessary; no automatic routing, more Modbus RTU slaves must be configured manually |
M200 | R220 | New housing, new operating temperature range. New housing: 6 DIN modules instead of 4 DIN modules. 8 more DOs. |
M210 | R220 | More outputs, however terminals and Modbus map are compatible with M210. Now 12 DOs, new housing and new operating temperature range. |
M300 | R320 | New housing, new operating temperature range. New housing: 6 DIN modules instead of 4 DIN modules. Small terminals instead of large terminals. |
M312 | R312 | New housing, new operating temperature range. |
M313 | R313 | New housing, new operating temperature range. |
M320 | R320 | New housing, new operating temperature range. Small terminals instead of large terminals. |
- | R330 | New type with 32 x DO, small terminals, 6 DIN modules housing |
M400 | R420 | New housing: 6 DIN modules instead of 4 DIN modules. Terminal reconnection necessary if module replaced. Modbus table not 100% compatible with that of M400. |
M401 | R420 | New housing: 6 DIN modules instead of 4 DIN modules. Terminal reconnection necessary if module replaced. Modbus table not 100% compatible with that of M400. |
M410 | - | NO REPLACEMENT. (230 V inputs) |
M411 | - | NO REPLACEMENT. (230 V inputs) |
M420 | R420 | Small terminals instead of large terminals. Common terminals for 8 and 8 inputs are now not separated. New housing, new operating temperature range. |
M430 | R430 | New housing, new operating temperature range. |
M500 | R500 | Small terminals instead of large terminals. DIPs for 0…20 mA at all inputs AI1-8. |
M504 | R560 | Small terminals instead of large terminals, different terminal positioning. Resistance measuring ranges added. Voltage: 0…10 V only. |
M560 | R560 | Small terminals instead of large terminals, different terminal positioning. DIPs for 0…20 mA at all inputs AI1-8. |
M610 | R610 | Different terminal positioning (standardisation with other modules), new housing, new operating temperature range. |
M620 | - | NO REPLACEMENT. (0…20 mA outputs only) |
M710 | R710 | Different positoining of terminals. New housing, new operating temperature range. |
FC010 | FCR010 | New housing, new operating temperature range. |
- | FCR011 | Same as FCR010, with 230 V AC power and 230 V AC valve outputs |
FC013 | FCR013 | New housing, new operating temperature range. |
FC015 | FCR015 | New housing, new operating temperature range. |