IPLC5xx – Process station MiniPLC shark

Actual version (24th April 2017, build 55278)

File downloadIPLC5xx – Process station MiniPLC shark

 

Release notes

2016.04.17 (build 55278)
NEW: Telecontrol driver editor(IEC 60870-5-104): Support for M_SP_TB_1 ASDU type (Single-point information with CP56Time2a time tag)
NEW: Telecontrol driver(IEC 60870-5-104): Support for M_SP_TB_1 ASDU type (Single-point information with CP56Time2a time tag)
NEW: RC File driver: http headers editor for web requests
BUG-FIX: RC File driver: fixed parsing of Int64 variables (Int32 range constraint)
NEW: M-Bus – new meter definitions added
NEW: Mbus: Signed BCD support
2016.04.06 (v 0.9.16.0406)
NEW: CommLynx(Danfoss): support for write to broadcast address (check parameters carefully!)
BUG-FIX: Buderus driver: communication fixed – commError handling (A5 response in normal mode, normal mode timeout does not cause commError); editor – parametr code fixed (hex format in xml definition), new params added to definition
BUG-FIX: SolarLog meteo: fix CRC option – accept wrong CRC under certain conditions
BUG-FIX: Elcor driver: Archive reading fixed – undocumented date format (bin vs BCD)

Runtime upgrade instruction:

Be aware, this instructions are for experienced engineer. If you have any doubts in the procedure described below, send device back to Domat Control System main office to upgrade device or call technical support.

Please backup all variables and PLC configuration first. Make sure that you have the current project, web, and LCD menu definition. Do not switch off power while uploading the runtime.

  • Connect to the device. Follow these instructions: http://domat-int.com/en/products/online-documentation/configuration-program-upload-iplc510
  • If the connection with the device trough WinSCP is established, upload enclosed softplcrt.sh folder to the root folder. Be aware that the folder must be transferred as binary (Right click on the folder, Upload ->Transfer settings)
  • Go to the PuTTY terminal window and press “q” (Quit to command line). Than enter command: sh softplcrt.sh
  • After this command, there are series of confirming dialogue. For common upgrade without configuration follow these instructions:

! WARNING ! This file overwrites existing files, continue (ay/N) ?  choose y
Keep old config file (AY/n) ? choose y
Old RT found. Delete (ay/N) ? choose y
Prerequisities complete. Ready to install. Continue (ay/N) ? choose y
File ‘functions.input.sh’ exists. Overwrite (AY/n) ? choose y
Enable DIP switch 1 (AY/n) ? choose y
Run license HW info generator (ay/N) ? choose n
Run softplc configurator (ay/N) ? choose n
Autostart SoftPLC RT (ano yes/no) ? choose y
Edit soft_plc.config (ano yes/no) ? choose y
Configure LCD menu (ano yes/no) ? choose n
Enable softplc watchdog (ay/N) ? choose y

  • If there is this notice after procedure: „Finished. Check everything and reboot.“, reboot the controller. Done.